Universal Xplorer Telecom Battery Monitor (UXTM)


A Real Time Battery Monitor Designed for Use in Telecommunications or in DC Powered Data Centers

● Automate the IEEE Recommended Practices for battery maintenance and testing

● Monitor up to four strings in parallel

● Robust design will monitor any 24V to 48V battery configuration

● Stay connected with Web enabled technology

● Multiple remote communications and alarm options

Monitor Critical Parameters Real Time

● Overall String Voltage

● Individual Cell/Block Voltages

● Individual Cell/Block Temperatures

● Ambient Temperature

● Discharge, Float, and Ripple Current

Proactive Battery State of Health Testing

● Tests the Entire Battery System's Integrity

● Internal Cell/Block Resistance Test

● Intercell and Intertier Connection Resistance Test

Stand Alone System

● No Onsite Computer is Required for Monitoring and Alarming

● Easily integrates to building management systems

● Embedded Web Server with Priority Email Scheduler

● 24x7 data collection, analysis, and remote alarm notification

Visit the Software Downloads section of our site for associated product software.>>

UXTM Specifications
System Measurements
Parameter Tolerance Number of Inputs
String Voltage 0 to 56 Volts Calculated
Discharge Current ±4000ADC ±1% of full scale Calculated
Ripple Current 0 to 250 Amperes RMS, ±5% of full scale Calculated
Float Current 0 to 5000mADC, ±1% of full scale, ±50mA Calculated
Ambient Temperature 0ºC to 80ºC±0.1ºC (32ºF to 176ºF) 1
Cell/Block Level Measurements
Cell Voltage 1V Range 0-4V 0.1% ±1mV
2V Range 0-4V 0.1% ±2mV
4V Range 0-6V 0.1% ±4mV
6V Range 0-9V 0.1% ±6mV
8V Range 0-12V 0.1% ±8mV
12V Range 0-18V 0.1% ±12mV
16V Range 0 to 24V 0.1% ±16mV
Intertier Resistance 0 to 5,000μΩ, 5% of reading ±5μΩ
Internal Cell Resistance 0 to 32,000μΩ, 5% of reading ±2μΩ
Intercell Resistance 0 to 5,000μΩ, 5% of reading ±5μΩ
Interier Resistance 0 to 5,000μΩ, 5% of reading ±5μΩ
Cell/Block Temperatures 0ºC to 80ºC ±0.1ºC (32ºF to 176ºF)

Agency Approvals

● UL60950-1, IEC60950-1, EN60950-1

● EN300 386, 2001 class B

● FCC part 15 class B

Operating Environment

● Temperature Range: 0ºC to 50ºC (32ºF to 122ºF)

● Humidity Range: 5% to 95% RH (noncondensing) at 0ºC to 32ºC

Digital Inputs

● 3 inputs configurable for dry or wet detection

Alarms

● Form C relay contact, 2A at 30VDC

Input Power

● DC Powered - 18 to 58VDC, 7.5W max

Communications

● RS485 - YDN-23 or MODBUS

● Ethernet - TCP/IP MODBUS or SNMP

● USB

Packaging

● 15.75”W x 1.75”H x 7.00”D

● Wall or 19” Rack Mount