TRUST YOUR BATTERIES™
  Technology and Solutions for Battery Testing
  Internal Resistance Baseline Guide    
 

These internal resistance baseline values from Alber research, battery manufacturers, and our customers will help determine the health of your batteries.

The average values in micro-ohms, taken on known-good batteries at 100% capacity, are to be used as guidelines only. Alber recommends you maintain baseline readings for your batteries based on manufacturers' data.

Taking Readings
When you take readings, you should record: Internal cell resistance; measuring instrument used, such as the Cellcorder; battery manufacturer, model and size (Ah); battery age; install date; date of test; and room temperature.

The batteries you measure should be either on-line or on-charge for at least 90 days. Connect the measuring instrument to the battery according to the equipment manufacturer's instructions, and observe the safety precautions below.

Listed readings are based on tests done at room temperature, typically 77F. Alber has observed that only extreme temperature variations affect cell resistance readings.

Contributing Your Readings
We would be pleased to add your resistance readings on 20 or more healthy batteries to our database. Your data should show: Internal cell resistance; measuring instrument used; battery manufacturer, model and size (Ah); battery age; install date; date of test; and room temperature. Or, if you have a Battery Analysis System ADF file, we can extract the data. To contribute your readings, contact our Engineering department or e-mail the ADF file.

Downloading a BLF File
You may download a file that contains resistance reference values for your CRT-300. This BLF battery list file for the Cellcorder BAS program has baseline data searchable by manufacturer and model number. If you already have battery baseline data, you should download then import the file, so your existing baseline data is not overwritten.

Safety Precautions
Hazardous voltages and chemicals may exist on batteries and in battery rooms and cabinets. Only qualified, properly trained personnel should conduct measurements on any battery. Always observe electrical safety precautions. Always wear safety glasses and protective clothing when required.


This data was updated on 16 July 2005. The values are subject to change as new data is received. Before measuring your batteries, read the safety precautions.


Internal Resistance Baseline Values


Manufacturer


Cell Model

Average
Resistance
(micro-ohms)

Alcad
   

Alcad

H22P

2331

Alcad

SD-5

1412

Alcad

SD-13

533

Alcad

XHP 28

1186

Alcad

XHP 36

775

Alcad

XHP 90

507

Americad
   

Americad

HED-30

1841

C&D
   

C&D

3DCU-5

2987

C&D

4LC-YC11

236

C&D

GC12V75A

6046

C&D

KRC-15

253

C&D

LS12-100

3666

C&D

MCT4000

100

C&D

TEL12-90

4237

C&D

TEL12-105F

4523

C&D

TEL12-125

3774

C&D

UPS12-100FR

8601

C&D

UPS12-140FR

6332

C&D

UPS12-170FR

7038

C&D

UPS12-225

5133

C&D

UPS12-270FR

4124

C&D

UPS12-300

3117

C&D

UPS12-370FR

3497

C&D

UPS12-475FR

3887

C&D

XT2LC23

128

C&D

XT4LC15

174

Caterpillar
   

Caterpillar

9G4231

3457

Caterpillar

9X9720

4858

DEKA East Penn
   

DEKA / East Penn

3AVR-85-23

263

DEKA / East Penn

3AVR-85-33

204

Douglas
   

Douglas

DGS12-150F

3183

Enersys
   

EnerSys

HR300

4181

EnerSys

HR500

3145

Exide
   

Exide

2DX-19

137

Exide

2GU-13

264

Exide

3CC-5

1688

Exide

EA-13

321

Exide

EC-19

221

Exide

ES-21

202

Exide

EU-7

664

Exide

GU-45

102

Fiamm
   

Fiamm

Monolite 45L8150

1458

GNB
   

GNB

90A13

427

GNB

90A21

215

GNB

100A33

180

GNB

100A87

191

Johnson Controls
   

Johnson Controls

FRB12-300

3994

Johnson Controls

GC12V75A

6046

Johnson Controls

UPS12-140FR

6332

Johnson Controls

UPS12-170FR

7038

Johnson Controls

UPS12-270FR

4124

Johnson Controls

UPS12-300

3117

Johnson Controls

UPS12-310FR

3324

Johnson Controls

UPS12-370FR

3497

Power
   

Power

PL-15

1996

Power

PRC-1225X

12908

Power

PRC-1235X

9033

Power

PRC-1250S

6222

Power

PRC-1250X

6484

Power

PRC-1250XL

7253

Power

PRC-1290X

4868

Power

PRC-12100X

4778

Power

PRC-12150X

3307

Power

SLF-12105

4764

Power

SLF-12205

2126

Power

TC-1250X

14181

Power

TC-1250XL

6594

Power

TC-12100X

10833

Power

TX-1280X

6341

Tudor
   

Tudor

LP105

2846

Yuasa
   

Yuasa

NP12-18

13704

Yuasa

NPG18-12FR

15099

Yuasa

NPX38

9309

Yuasa

NPX100R

13396

Yuasa

NPX150

8799

Yuasa

NPX150-12R

8464

Yuasa

NPX150R

8535

Yuasa

DM55-12FR

7311

 

 

| What's New | Home | About Us | Products | Services | Seminars | Sales Reps | Tech Library |
| Updates | Training | Contact |

All content is the property of Albercorp.
Reproductions and/or copies of this web site, in whole or in part,
are strictly forbidden without prior written consent of Alber.
'Trust Your Batteries' and the Alber logo are trademarks of Albercorp.
Battcon is a registered trademark of Albercorp.
Alber
3103 No. Andrews Ave. Ext.
Pompano Beach, Florida
33064
(954) 623-6660

Last updated 16 July 2005
Copyright ©2010 Albércorp